;===================================================================== ; GSD file for 2600T Pressure Series Transmitter - Mod.262/264 - PROFIBUS-DPV1 ; Company: ABB SACE SpA ; Version: 1.0 ; Date: 20.01.2003 ; Author: M.Romagnoli Tel +39 344 58248 ; Fax +39 344 56152 ; E-mail mauro.romagnoli@it.abb.com ; ;==================================================================== ; GSD File (Simple compact Slave) ; ; Version: V0.1 ;====================================================== #Profibus_DP GSD_Revision=2 ;General parameters Vendor_Name = "ABB" Model_Name = "2600T Press. Transm. 262/264" Revision = "1.00" Ident_Number = 0x052B Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release= "V 1.00" Software_Release= "V 1.00" Implementation_Type="SPC42/ITEC" Bitmap_Device="262_264N" Bitmap_Diag="262_264D" Bitmap_SF="262_264S" 9.6_supp = 0 19.2_supp = 0 31.25_supp = 1 45.45_supp = 1 ; for Siemens Segment Coupler 93.75_supp = 1 ; for Pepperl & Fuchs Segment Coupler 187.5_supp = 0 500_supp = 0 1.5M_supp = 0 3M_supp = 0 6M_supp = 0 12M_supp = 0 MaxTsdr_31.25 = 100 MaxTsdr_45.45 = 200 MaxTsdr_93.75 = 1000 Redundancy = 0 Repeater_Ctrl_Sig = 2 24V_Pins = 0 ; Slave-Specification: Freeze_Mode_supp = 0 Sync_Mode_supp = 0 Auto_Baud_supp = 0 Set_Slave_Add_Supp = 1 Min_Slave_Intervall = 100 Fail_Safe = 1 Max_Diag_Data_Len = 20 Slave_Family = 12 Modular_Station = 1 Max_Module = 4 Max_Input_Len = 10 Max_Output_len = 0 Max_Data_Len = 10 ; UserPrmData: Length and Preset: User_Prm_Data_Len = 3 User_Prm_Data = 0x00,0x00,0x00 ;----------- Description of device related diagnosis: --------------------- ; Unit_Diag_Bit(16) = "Error appears" Unit_Diag_Bit(17) = "Error disappears" Unit_Diag_Bit(24) = "Hardware failure electronics" Unit_Diag_Bit(25) = "Hardware failure mechanics" Unit_Diag_Bit(28) = "Memory error" Unit_Diag_Bit(29) = "Measurement failure" Unit_Diag_Bit(34) = "Configuration invalid" Unit_Diag_Bit(35) = "Restart" Unit_Diag_Bit(36) = "Coldstart" Unit_Diag_Bit(37) = "Maintenance required" Unit_Diag_Bit(39) = "Ident_Number violation" Unit_Diag_Bit(55) = "Extension Available" ;-- diagnosisExtension[0] Unit_Diag_Bit(56) = "Sensor incompatible" Unit_Diag_Bit(57) = "Sensor data-base incompatible" Unit_Diag_Bit(58) = "Memory CRC critical error" Unit_Diag_Bit(59) = "Memory CRC not-critical error" Unit_Diag_Bit(60) = "Read Only Memory failed" Unit_Diag_Bit(61) = "Sensor EEPROM burn failed" Unit_Diag_Bit(62) = "Electronic EEPROM burn failed" ;-- diagnosisExtension[1] Unit_Diag_Bit(64) = "Pressure Sens.Out of High limit" Unit_Diag_Bit(65) = "Pressure Sensor Out of Low limit" Unit_Diag_Bit(66) = "Overrange High side" Unit_Diag_Bit(67) = "Overrange low side" Unit_Diag_Bit(68) = "Sensor Temp.Out of High limit" Unit_Diag_Bit(69) = "Sensor Temp.Out of Low limit" Unit_Diag_Bit(70) = "Static Pressure Out of limit" ;-- diagnosisExtension[2] Unit_Diag_Bit(72) = "Static Pressure sensor failed" Unit_Diag_Bit(73) = "Sensor Temperature sensor failed" Unit_Diag_Bit(74) = "Simulation Active" ;------------------------------------------------------------------------- ; Module Definition List Module="PV status (short)" 0x94 EndModule Module="PV status" 0x42,0x84,0x08,0x05 EndModule Module="PV & Auxiliary (short)" 0x94,0x94 EndModule Module="PV & Auxiliary" 0x42,0x84,0x08,0x05,0x42,0x84,0x08,0x05 EndModule